Allen-Bradley Auxiliary Contacts used with 12-Pulse Drive on IMC-SCR and IMC-PERFORMA Control Systems

Advisory

Date

January 23, 2002

Reference

126

Route to

Service Manager/Modernization Manager

From

MCE Technical Support Department

Description

Intermittent car shutdown with a fault log entry "No Response for Run Request."

Details

MCE has recently discovered that Allen-Bradley experienced a manufacturing anomaly on their auxiliary contacts used with MCE's 12-Pulse drive. The contact material in a small number of auxiliary contacts does not have enough "wipe" to make with 100% reliability. The result is an intermittent contact that can cause the fault described above. Allen-Bradley has remedied this situation and all controllers shipped from MCE beginning in 2002 will have the corrected auxiliary contacts.

Action

f you are experiencing the fault described above, please call MCE Technical Support for troubleshooting assistance. MCE will provide replacement auxiliary contacts once the diagnosis has been confirmed.